Description
-
BrandGE
-
ModelIS220PTURH1B
-
Product NameTurbine Specific Primary I/O Trip Pack
-
Place of OriginUnited States
-
HS Code85371090
-
Dimensions40 mm × 80 mm × 120 mm
-
Weight0.40 kg
-
Operating Temperature0 °C to +60 °C
-
Storage Temperature-40 °C to +85 °C
-
Power Supply24VDC
-
Warranty12 month
-
Product StatusNew and original
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
Module Power Supply
This module requires an external DC power source for operation. The nominal supply voltage is 28 VDC, with the allowable operating voltage range spanning from 27.4 VDC to 28.6 VDC. The maximum input current reaches 0.41 A under full operating load, and the overall maximum power consumption of the module is limited to 25 W to ensure stable long-term operation within the control cabinet.
Field Signal Inputs
Emergency Stop Input accepts signal voltage ranging from 18 VDC to 140 VDC for safety interlock signal acquisition.
Voltage Protection Trip Inputs support input voltages between 16 VDC and 140 VDC to monitor critical trip trigger signals.
Magnetic Speed Pickup Inputs are designed to process pulse signals within the voltage range of -15 VDC to +15 VDC for rotational speed detection.
Trip Contact Output
The relay contact output features a rated switching voltage range of 24~28 VDC. It supports a maximum switching current of 7 A, capable of driving external trip circuits and related field actuation devices.
Fault 1: PWR LED Remains Off, Module Cannot Boot Normally
Possible Causes
The supplied 28 VDC power deviates from the specified operating range of 27.4~28.6 VDC
Loose power terminals, defective cable contacts or broken power wires
Internal short circuit on the module circuit leading to abnormal power draw
Solutions
Measure the input voltage to verify compliance with specifications. Retighten power terminals and inspect cable integrity. Remove and reinstall the module securely onto the TTURH1C terminal board. If the issue persists after wiring inspection, replace the module for testing. Ensure the input current never exceeds the maximum rating of 0.41 A.
Fault 2: Flashing ENET LINK LED or Loss of Communication with Mark VIe Controller
Possible Causes
Damaged Ethernet cable, poor RJ45 contact or incorrect network wiring layout
Mismatched network parameters between the module and main controller
Incompatible or corrupted module firmware
Electromagnetic interference disrupting data transmission
Solutions
Swap out the cable with a fully tested Ethernet line and reseat RJ45 plugs. Download compatible firmware via Toolbox software and double-check IP addresses and redundancy configurations. Route network cables separately from high-power cables and implement standard shielding and grounding to mitigate interference. Restart the module after finishing parameter adjustments.
Fault 3: Loss of Magnetic Speed Pickup Input, Incorrect Speed Readings and Pulse Error Alarms
Possible Causes
Damaged magnetic pickup sensor or improperly adjusted sensor air gap
Open circuits, short circuits or inadequate shielding of signal cables
Insufficient signal amplitude to meet the receiving threshold at low rotation speeds
Loose connectors on the terminal base
Solutions
Check and calibrate the mounting clearance of the magnetic pickup transducer and test its output waveform. Verify wiring continuity and troubleshoot short-circuit issues. Rearrange cable paths to stay away from interference sources. Adjust the trigger threshold for speed signals via configuration software and firmly lock all terminal connectors.
Fault 4: Failure to Detect Emergency Stop / Trip Input Signals
Possible Causes
Field input voltage outside the valid working range of 18~140 VDC
Open circuits within the E-stop loop or loose wiring terminals
Oxidized contacts on external emergency stop relays
Solutions
Measure the field signal voltage and test the continuity of the entire emergency stop circuit. Clean or replace aging relay contacts. Secure all wiring terminals mounted on the TTURH1C base terminal board.
Fault 5: Trip Contact Output Fails to Activate the Load Circuit
Possible Causes
Load voltage exceeds the rated 24~28 VDC operating range
Load current surpasses the maximum 7 A rating and triggers internal relay protection
Degraded internal trip relay contacts or broken output wiring
Solutions
Confirm load voltage and current are within the module’s rated specifications. Install an intermediate relay for current expansion if the load draws excessive current. Inspect continuity of output wiring. Replace the module if internal relay contact failure is confirmed.
Fault 6: Occasional Random Failures and Unstable Signal Acquisition
Possible Causes
Poor physical contact between IS220PTURH1B and the terminal base
Improper system grounding and severe electromagnetic interference
Excessive ambient temperature resulting in unstable module performance
Vibration loosening wiring terminals over time
Solutions
Cut off power supply, pull out and reinsert the module completely. Optimize cabinet grounding layout and separate signal cables from power cables. Enhance cabinet ventilation to regulate ambient operating temperature. Retighten all terminals and add anti-vibration reinforcements for the control cabinet.
Fault 7: Unable to Download Configuration; Settings Lost After Power Cycle
Possible Causes
Firmware version incompatible with the Mark VIe system
Faulty internal non-volatile memory of the module
Communication interruption occurring during configuration download
Solutions
Install the officially matched firmware version. Prevent power loss during program downloading. Re-transfer all configuration parameters and conduct power cycle verification. Replace the module if configurations still cannot be stored reliably.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms