Description
-
BrandGE
-
ModelC60G01HCHF8FH6PM8FP6PU6PWXX
-
Product NameMultilin C60 Breaker Protection & Control Relay
-
Place of OriginCanada
-
HS Code85371011
-
Dimensions250mm × 220mm × 40mm
-
Weight2.3kg
-
Operating Temperature-40℃ to +85℃
-
Storage Temperature-50℃ to +90℃
-
Power Supply85–264 VAC / 88–300 VDC
-
Warranty12 month
-
Product StatusNew and original
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
1. Main Control Power Supply
AC Power Option
Nominal input: 100~240 VAC, 50/60 Hz
Working tolerance range: 88~265 VAC, adaptable to 25~100 Hz
Rated power consumption: 45 VA
Built-in fuse rating: 4 A, 250 VAC
DC Power Option
Nominal input: 24~48 VDC
Minimum activation voltage: 17 VDC for 24 VDC mode, 33 VDC for 48 VDC mode
Built-in fuse rating: 8 A, 250 VDC
2. Analog Input (CT, PT and DC Analog Signals)
CT secondary input: rated 1 A / 5 A, burden load less than 0.2 VA; withstands 250 times rated current within 20 ms.
Programmable DC analog current input ranges: 0~1 mA, ±1 mA, 0~5 mA, 0~10 mA, 0~20 mA, 4~20 mA; input impedance is 379 Ω with ±10% tolerance.
RTD temperature measurement: constant excitation current of 5 mA.
3. Relay Output Ratings
DC Inductive Load (L/R = 40 ms)
24 VDC: max 0.5 A
48 VDC: max 0.5 A
125 VDC: max 0.3 A
250 VDC: max 0.2 A
AC Resistive Load
250 VAC: maximum continuous current 5 A
Short-duration surge current tolerance: 30 A for 0.2 seconds
4. Digital Discrete Input
Dry contact pickup current: 80~100 mA
Dielectric isolation withstand voltage: 2 kV

1. Pre-Commissioning Preparation & Static Inspection
Cut off all AC/DC power and CT/PT secondary loops, implement safety protection and anti-static measures.
Inspect device appearance, keys and indicators; verify all power, control and trip wiring conforms to drawings with no loose connections or short circuits.
Test loop insulation resistance with a megohmmeter (qualified: ≥100 MΩ).
Prepare EnerVista UR Setup software, matching firmware, protection settings, logic documents and wiring diagrams.
2. Power-On Check & Hardware Self-Test
Perform graded power-on test per AC/DC voltage range, confirm normal display and no abnormal alarms or overheating during automatic 30s self-test.
Verify front panel keys, page switching, alarm reset functions and calibrate the system clock.
Run built-in hardware diagnosis to confirm CPU, sampling board, communication and output modules work normally, then clear historical fault logs.
3. Communication Setup & System Configuration
Establish PC connection with the device via Ethernet or RS485, and unify network segment parameters.
Connect via EnerVista UR Setup, verify the full device model, and back up the factory configuration.
Configure passwords, operation permissions, Modbus/DNP3 communication parameters, clock synchronization and alarm storage parameters.
4. Sampling Loop Calibration
Calibrate CT sampling (1A/5A rated input) and PT voltage sampling to ensure error ≤±0.5%.
Verify 4~20mA/0~10mA analog sampling accuracy and RTD 5mA constant current detection function.
Test dry contact digital inputs to confirm reliable status identification under standard trigger current (80~100mA).
5. Protection Setting & Functional Verification
Download and lock project protection settings including overcurrent, overload, overvoltage, undervoltage and earth fault protection.
Simulate various fault conditions via relay tester; control protection action error within ±5% and time error within ±20ms.
Verify trip and alarm relay contacts meet rated load specifications with reliable closing and resetting performance.
6. FlexLogic Custom Logic Commissioning
Import customized interlock logic via software, simulate all trigger conditions to check logic consistency.
Verify linkage of virtual logic with physical I/O and remote control functions.
Solidify qualified logic to the device and complete repeated stability tests.
7. Communication & Remote Function Debugging
Connect with DCS/SCADA system to test stable Modbus TCP and DNP3 data upload without packet loss.
Verify remote parameter modification, fault query and firmware upgrade functions.
Complete pairing and debugging for optional HardFiber remote units.
8. Comprehensive Simulation & Stability Test
Simulate complex system faults to check accurate protection action and complete event recording.
Implement 24-hour continuous power-on aging test to ensure stable operation without restart or false action.
Complete on-site circuit breaker linkage test for trip and reclosing coordination verification.
9. Data Backup & Project Handover
Back up all configurations, fixed values, logic programs and fault logs.
Sort out commissioning data and complete acceptance documents.
Restore the device to formal operating state, open monitoring authority and lock parameter modification authority.
Finish on-site technical training and hand over all drawings, manuals and backup files.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms