Description
-
BrandBently Nevada
-
Model1900/65A-01-01-04-CN-00
-
Product Name1900/65A General Purpose Equipment Monitor
-
Place of OriginUnited States
-
HS Code85437099
-
Dimensions196.9 mm × 149.4 mm × 74.4 mm
-
Weight0.77 kg
-
Operating Temperature-20 °C ~ +70 °C
-
Storage Temperature-30 °C ~ +90 °C
-
Power Supply110–220 V AC, 50/60 Hz
-
Warranty12 month
-
Product StatusNew and original
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
Main Power Supply
Operating voltage range: 18 VDC ~ 36 VDC, nominal 24 VDC
Typical operating current: 0.3 A
Built-in reverse polarity protection
Transducer Sensor Power Supply
Two-wire sensor drive: Constant current 3.3 mA ±5%, open-circuit voltage 21~24 VDC
Three-wire proximity sensor power: -24.02 ~ -23.47 VDC, max channel current 15 mA
4–20 mA Analog Output (4 channels)
Signal range: 4 ~ 20 mA
Maximum allowable loop resistance: 600 Ω
External loop supply range: 18 ~ 36 VDC
Relay Contact Output (6 programmable relays)
Resistive AC load: 250 VAC / 5 A
Resistive DC load: 60 VDC / 5 A
Max switching power: 150 VA
Buffered Signal Output
Low-impedance vibration signal output, short-circuit protected, no heavy current load capability
Temperature Inputs
Supports RTD and thermocouple signals; low-level millivolt input without large load current
Digital Control Inputs (Inhibit / Reset)
High impedance input, operating voltage 18~36 VDC, tiny quiescent current

Visual Inspection
Examine the monitor housing, display screen and status indicators for physical damage, dust buildup and overheating marks. Check all terminal blocks, sensor cables and connectors for looseness, oxidation and oil contamination. Confirm the unit is securely mounted on the DIN rail and will not shift under vibration.
Environment Inspection
Make sure the temperature and humidity inside the cabinet meet operating requirements. Keep the surrounding environment away from corrosive gas, excessive dust and strong electromagnetic interference. Prevent direct sunlight from irradiating the display panel.
Power Supply Inspection
Measure the input DC voltage to guarantee it remains within the range of 18–36 VDC. Troubleshoot voltage fluctuation and bad contact issues, and verify the normal operation of reverse polarity protection.
Sensor & Signal Circuit Maintenance
Inspect wiring of proximity probes, accelerometers and RTD sensors. Check shielding and grounding conditions; single-point grounding shall be implemented on the monitor side. Check triaxial connectors to prevent ingress of moisture and dirt.
I/O Channel Inspection
Monitor the operating status and loop resistance of 4–20mA analog output circuits. Check relay output terminals for ablation. Conduct periodic tests on relay actuation and alarm response during equipment shutdown.
Communication & Data Management
Ensure stable data communication with the upper monitoring system. Regularly download event logs, fault records and trend data for anomaly analysis. Back up configuration files of the monitor.
Self-diagnosis Check
Check built-in self-test results through the local keypad or configuration software. Timely resolve sensor failures, signal open circuits and internal hardware alarms.
Cleaning Requirements
Clear surface dust using a dry soft brush. Avoid spraying liquid cleaning agents directly onto the module to prevent circuit corrosion.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms.
7.Do you offer warranty on industrial control spare parts?
Warranty differs by product.
Confirm specific warranty details with us prior to ordering.
8.Are your automation parts new or used?
We supply both new and fully tested used industrial control spare parts.
Please state your needs in your inquiry.
9.What is your typical delivery lead time?
In-stock items can be shipped quickly.
We will advise exact lead time for out-of-stock products after stock verification.
10.Can you offer technical support to check model compatibility?
Yes.Our professional team provides technical support to verify specifications and model compatibility.