BrandGE
-
ModelDS200TDAH1BHD
-
Product NameDigital I/O Board
-
Place of OriginUnited States
-
HS Code8537101190
-
Dimensions280mm × 213mm × 34mm
-
Weight1.21 kg
-
Operating Temperature-20°C ~ +70°C
-
Storage Temperature-40°C ~ +85°C
-
Power Supply24VDC
-
Warranty12 month
-
Product StatusNew and original
Backed by abundant in-stock inventory and nearly 20 years of industry experience, our company stands as a leading player in the industrial control sector.We offer an extensive range of industrial control products covering numerous models. Should you have any other requirements, please feel free to contact us, and we will respond to you promptly.
Our main brand:
1.ABB's module cards, touch screens, controllers, etc., such as PP846 touch screen, IGCT starting with 5SHY, PM starting controller, AI, DO starting input/output module, SP starting Bailey module, etc
2.GE's module card CPUs, such as VMIC starter, IS200, IS215, IS400, IS420 series, etc,
3.Emerson's card components and EPRO probes, Westinghouse 1C series, Honeywell CC series, Schneider 140 series, Envision full series, Bentley 3500 series, Rexroth motors and drives, and Foxboro small modules.
Power Supply:
Nominal backplane supply: 28 VDC; operating range: 18 VDC ~ 32 VDC
Typical board operating current: 0.42 A
Digital Signal Specifications:
Digital Input Rated Voltage: 24 VDC
Digital Output Driving Voltage: 24 VDC
Maximum continuous current per discrete output channel: 180 mA
Communication Circuit:
IONET communication powered by 5 VDC onboard circuit
Signal Isolation Rating:
Field signal to internal logic isolation: 250 VAC

Pre-Wiring Preparation
Carry out Lockout/Tagout (LOTO) procedures and disconnect cabinet power. Wear a grounded ESD wrist strap. Take photos of original jumper layouts and cable arrangements for reference, and prepare engineering schematics and signal allocation tables.
Backplane Installation
Insert the module into the specified rack slot and secure it tightly to achieve stable 28 VDC backplane power supply (operating range: 18–32 VDC). Do not apply excessive force to prevent bent backplane pins.
Inter-Board Ribbon Cable Wiring
JQ (50-pin): Connect to the DS200DTBA terminal board for digital contact input signals;
JR (50-pin): Connect to the DS200DTBB terminal board for field discrete input signals;
JO1 & JO2: Wire to TCRA boards for digital output driving signals;
JX1, JX2 (3-pin): Daisy-chain IONET communication cables to realize data interaction with core processor boards.
Align the notch of ribbon connectors correctly and avoid reverse connection.
Field Signal Wiring Specifications
All field discrete signals are wired to DTBA/DTBB terminal boards instead of directly connecting to the TCDAH1BHD board.
Digital Input: 24 VDC contact signals including interlock status, fault feedback, limit switch signals and trip contacts; polarity must be strictly observed.
Digital Output: 24 VDC driving signals for relays, solenoid valves and alarm equipment; the maximum continuous current of each channel is 180 mA.
Keep signal cables separated from high-power cables. All shielded cables shall adopt single-point grounding to mitigate electromagnetic interference.
Onboard Jumper Setup Before Power-Up
Configure 8 onboard jumpers (JP1–JP8) to set input polarity, signal debounce time and fault detection modes in accordance with site drawings. Ensure jumper settings comply with control logic demands.
Post-Wiring Inspection
Check that all ribbon cables are fully locked. Inspect terminals for tight connections, short circuits and open circuits. Remove any conductive foreign objects on the PCB.
Restore power gradually and measure the 28 VDC backplane voltage.
Perform channel loop testing: input simulated discrete signals, confirm consistent signal readings on Mark V Toolbox and test every output channel.
Archive wiring diagrams and jumper configuration records for maintenance.
Critical Warnings
Hot swapping of the board under energized conditions is prohibited.
Improper wiring of JQ/JR will cause signal loss and abnormal protection logic.
The load current of each digital output channel cannot exceed 180 mA to prevent circuit damage.

Frequently Asked Questions (FAQ)
1.How fast will you reply to my inquiry?
We process all inquiries efficiently and will respond promptly once we receive your message.
2.Do you carry large inventory of industrial control parts?
We maintain massive ready stock of mainstream automation spare parts to shorten lead times.
3.Can you source discontinued or obsolete PLC & DCS modules?
Absolutely.
We specialize in sourcing hard-to-find, obsolete and out-of-production industrial control components.
4.Do you inspect goods before shipment?
Every product undergoes thorough inspection before packing and dispatch.
5.Can you ship orders worldwide?
We provide global shipping with flexible logistics for urgent and regular orders.
6.What payment methods are available?
We accept multiple secure payment options. Please contact our sales team for detailed terms.